Check the free-air flow
The required free-air flow is 2,000 L/min, or about 70.6 CFM. Use the compressor’s delivered flow at the operating pressure. As a separate check in the fill calculator, a 500 L receiver going from 6 to 7 bar gauge at this flow takes about 15 seconds in the simplified model, with no downstream demand.
Calculate the minimum internal diameter
Enter 2,000 L/min of free air, 7 bar gauge, 20 °C and a target velocity of 8 m/s. The calculator gives about 253 L/min at line conditions and a minimum internal diameter of 25.9 mm. Use actual internal diameters from the pipe supplier.
Compare pressure drop for 26 and 32 mm
Carry over the same flow, pressure and temperature. Enter a 100 m run, 0.045 mm roughness and a total fittings loss coefficient K of 8. The estimated loss is 0.302 bar at 26 mm and 0.107 bar at 32 mm. For an illustrative loss budget of 0.2 bar, only the 32 mm option meets the budget. Use the pressure required at the point of use to set your own limit.
Estimate the annual leak cost
For a separately measured leak of 200 L/min, assume a compressor specific power of 7 kW per (m³/min), 4,000 pressurized hours per year and a tariff of €0.15/kWh. This gives about 1.4 kW, 5,600 kWh and €840 per year. Use measured leak flow and the actual tariff for your installation.